USD

AddressCompany:Shenzhen Tuoli Electronic Technology Co.,Ltd.
Address:Floor 6, Building B, Baifuli Industrial Park, Shanghenglang Industrial Zone,
Dalang Street, Longhua District, Shenzhen
Service Hotline:008618899777586 (WhatsApp)
E-mail:Service@tuolitech.com


Fluke 3000 FC HVAC System work on electrical panels faster safer easier with remote current and temperature modules

Copy and share this link on social network or send it to your friends

Copy

Fluke 3000 FC HVAC System work on electrical panels faster safer easier with remote current and temperature modules Item NO.: 543247

Write a Review
US$ 556.66
Quantity:
Stock ( 9999999 )
Shipping Cost:
Estimate Shipping Cost
Product Name Fluke 3000 FC HVAC System work on electrical panels faster safer easier with remote current and temperature modules
Item NO. 543247
Measuring testers Current tester/Ammeter, Thermomether
Weight 1.8 kg = 3.9683 lb = 63.4931 oz
Category Phone repair tools
Tag 3000 FC , 3000 , current tester , current meter , thermometer
Brand FLUKE
Creation Time 2019-09-09

Product overview: Fluke 3000 FC HVAC System



The Fluke FC Wireless HVAC System lets you work on electrical panels faster, safer, easier with remote current and temperature modules

Connect your FC AC Wireless Current Clamp Module to your test point, and view the results up to 20 meters away on the FC Wireless Digital Multimeter. Plus, you can connect the t3000 FC Wireless K-Type wireless temperature module and view remote temperature measurements.

You’ll save time, with less run-around collecting multiple measurements. Use multiple modules for measurements on three-phase systems, as a stand-alone measurement tool or combine with other Fluke Connect™ modules as a system for multiple measurements.

From short distances, you can even view readings from modules through closed electrical panels. Plus no more writing down data as the Fluke Connect remote modules captures up to 65,000 sets of time stamped min/max/avg readings, using the optional PC adapter. Fluke Connect wireless test tools also offer increased safety by letting you view readings in a separate location from the test point.

Now you can take readings on moving machinery, with only the measurement module in harm’s way.


Specifications: Fluke 3000 FC HVAC System

Fluke 3000 FC Series Wireless Multimeter

* For all specifications: accuracy is specified for one year after calibration, at operating temperatures of 18°C to 28°C, with relative humidity at 0% to 90%. Accuracy specifications take the form of ±([% of Reading ] + [Number of least significant digits]).

Detailed Specifications
AC Voltage
Range ¹ / Resolution 600.0 mV / 0.1 mV
6.000 V / 0.001 V
60.00 V / 0.01 V
600.0 V / 0.1 V
1000 V / 1 V
Accuracy 234 45 Hz to 500 Hz 1.0% + 3
500 Hz to 1 kHz 2.0% + 3
1. All AC voltage ranges are specified from 1% of range to 100% of range.
2. Crest factor of ≤ 3 at full scale up to 500 V, decreasing linearly to crest factor < 1.5 at 1000 V.
3. For non-sinusoidial waveforms, add ±(2% of reading + 2% full scale) typical, for crest factor up to 3.
4. Do not exceed 107 V-Hz.
DC Voltage, Continuity, Resistance, Diode Test and Capacitance
Function
mV Range / Resolution 600.0 mV / 0.1 mV
Accuracy 0.09% + 2
V Range / Resolution 6.000 V / 0.001 V
60.00 V / 0.01 V
600.0 V / 0.1 V
1000 V / 1 V
Accuracy 0.09% + 2
0.15% + 2
))) Range / Resolution 600 Ω / 1 Ω
Accuracy Meter beeps at < 25 Ω, beeper detects opens or shorts of 250 μs or longer.
Ω Range / Resolution 600.0 Ω / 0.1 Ω
6.000 kΩ / 0.001 kΩ
60.00 kΩ / 0.01 kΩ
60.00 kΩ / 0.1 kΩ
600.0 kΩ / 0.001 MΩ
50.00 MΩ / 0.01 MΩ
Accuracy 0.5% + 2
0.5% + 1
1.5% + 3
Diode test Range / Resolution 2.000 V / 0.001 V
Accuracy 1% + 2
µF Range / Resolution 1000 nF / 1 nF
10.00 μF / 0.01 μF
100.0 μF / 0.1 μF
9999 μF1 / 1 μF
Accuracy 1.2% + 2
10% typical
1 In the 9999 μF range for measurements to 1000 μF, the measurement accuracy is 1.2% + 2.
AC and DC Current
Function
mA AC
(45 Hz to 1 kHz)
Range 1 / Resolution 60.00 mA / 0.01 mA
400.0 mA 3/ 0.1 mA
Accuracy 1.5% + 3
mA DC 2 Range 1 / Resolution 60.00 mA / 0.01 mA
400.0 mA 3/ 0.1 mA
Accuracy 0.5% + 3
1. All AC current ranges are specified from 5% of range to 100% of range.
2. Input burden voltage (typical): 400 mA input 2 mV/mA.
3. 400.0 mA accuracy specified up to 600 mA overload.
Frequency
Range / Resolution 99.99 Hz / 0.01 Hz
999.9 Hz / 0.1 Hz
9.999 kHz / 0.001 kHz
99.99 kHz / 0.01 kHz
Accuracy 1 0.1% + 1
1 Frequency is specified up to 99.99 kHz in volts and up to 10 kHz in amps.
Input Characteristics
Function Overload
protection
Input impedance
(nominal)
Common mode rejection ratio (1 kΩ unbalance) Normal mode rejection
1100 Vrms > 10 MΩ < 100 pF > 120 dB at DC, 50 Hz or 60 Hz > 60 dB at 50 Hz or 60 Hz
1100 Vrms > 10 MΩ < 100 pF > 60 dB, DC to 60 Hz > 60 dB at 50 Hz or 60 Hz
1100 Vrms > 10 MΩ < 100 pF > 120 dB at DC, 50 Hz or 60 Hz > 60 dB at 50 Hz or 60 Hz
Open circuit test voltage Full scale voltage Typical short circuit current
To 6 MΩ 50 MΩ Typical short circuit current
1100 Vrms < 2.7 VDC < 0.7 VDC < 0.9 VDC < 350 mA
1100 Vrms < 2.7 VDC 2.000 VDC < 1.1 mA
mA Function
Overload protection Fused, 44/100 A, 1000 V FAST Fuse
Overload 600 mA overload for 2 minutes maximum, 10 minutes rest minimum
MIN/MAX Recording Accuracy
DC functions The specified accuracy of the measurement function ±12 counts for changes > 350 mS in duration.
AC functions The specified accuracy of the measurement function ±40 counts for changes > 900 mS in duration.
General Specifications
Maximum voltage between any terminal and earth ground 1000 VDC or AC rms
Ω fuse protection from A inputs 0.44 A (44/100 A, 440 mA), 1000 V FAST Fuse, Fluke specified part only
Display (LCD) Update rate 4/sec
Volts, amps, ohms 6000 counts
Frequency 10,000 counts
Capacitance 1,000 counts
Battery type Three AA Alkaline batteries, NEDA 15A IEC LR6
Battery life 250 hours minimum
RF communications 2.4 GHZ ISM Band
RF communication range Open air, unobstructed Up to 20 m
Obstructed, sheetrock wall Up to 6.5 m
Obstructed, concrete wall, or steel electrical enclosure Up to 3.5 m
Temperature Operating -10°C to 50°C
Storage -40°C to 60°C
Temperature coefficient 0.1 x (specified accuracy) / °C (< 18°C or > 28°C)
Relative humidity 0% to 90% (0°C to 35°C)
0% to 75% (35°C to 40°C)
0% to 45% (40°C to 50°C)
Altitude Operating 2,000 m
Storage 12,000 m
Electromagnetic compatibility
EMI, RFI, EMC, RF
EN 61326-1:2006, EN 61326-2-2:2006
ETSI EN 300 328 V1.7.1:2006, ETSI EN 300 489
V1.8.1:2008,
FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249
FCCID : FCC: T68-FDMMBLE IC: 6627A-FDMMBLE
Safety compliance ANSI/ISA 61010-1 / (82.02.01): 3rd edition
CAN/CSA-C22.2 No 61010-1-12: 3rd edition
UL 61010-1: 3rd edition
IEC/EN 61010-1:2010
Certifications CSA, FCC, CE
Ingress Protection (IP) rating IP54
Pollution Degree 2
Size (H x W x L) 4.75 x 9.3 x 20.7 cm (1.87 x 3.68 x 8.14 in)
Weight 340 g (12 oz)
Warranty Three years
Not compatible with Fluke CNX test tools
 

Fluke a3000 FC Wireless AC Current Clamp Module

Specifications
Range 0.5 A to 400.0 A
Resolution 0.1 A
Accuracy 400.0 A: 2% ±5 digits (10 Hz to 100 Hz) 2.5% ±5 digits (100 Hz to 500 Hz)
Inrush Max displayed reading 999.9A
Crest factor (50 Hz / 60 Hz) 3 at 500 A
2.5 at 600 A
1.42 at 1000 A
add 2% for C.F. > 2
LCD w/ backlight 3½ digits
Log rate/interval 1 sec minimum/adjustable by PC
Battery type 2 AA, NEDA 15 A, IEC LR6
Battery life 400 hours
Memory Record up to 65,000 readings
RF communications 2.4 GHZ ISM Band
RF communication range Open air, unobstructed Up to 20 m
Obstructed, sheetrock wall Up to 6.5 m
Obstructed, concrete wall or steel electrical enclosure Up to 3.5 m
Operating temperature -10°C to +50°C
Storage temperature -40°C to +60°C
Temperature coefficient Add 0.1 x (specified accuracy) / °C (< 18°C or > 28°C)
Operating humidity 90% at 35°C
75% at 40°C
45% at 50°C
Altitude Operating 2,000 m
Storage 12,000 m
EMC EN 61326-1:2006
Safety compliance IEC 61010-1, 600 V CAT III, 3rd edition Pollution Degree 2
Safety rating CAT III 600 V
Certifications CSA, CE, FCC: T68-FBLE IC: 6627A-FBLE
Ingress Protection (IP) rating IP30
Pollution Degree 2
Jaw opening 34 mm (1.33 in)
Size (H x W x D) 20.3 x 7.49 x 3.55 cm (8 x 2.95 x 1.4 in)
Weight .22 kg (8 oz)
Warranty Three years
Not compatible with Fluke CNX test tools
 

Fluke t3000 FC Wireless K-Type Temperature Module